Skip to the end of the images gallery Previous Next12 Reset Skip to the beginning of the images gallery Details Cartridge fire dampers are designed and have CE mark�in accordance with EN 15650 and certified to comply with the EI-S (EN 1366-2) performance attributes. PKI-C fire dampers are designed to be embedded into the ducts in the�fire partition walls, or at the end of a duct in front of the valve. Installation of these devices is described in PP-74_PKI-C_EN-DE-FR-NL-IT.pdf in Documentation tab. As a standard, all the dampers are supplied in a basic version, with a microswitch, or accessories - cover plates . The fire damper automatically sets itself to a �CLOSE" position if the thermal fuse link gets ruptured. After the closure, the damper blade is mechanically secured in the closed position and can only be opened manually, which requires access of the maintenance staff into the duct. To improve the duct accessibility for fire damper inspection purposes, we supply a flexible coupling as an accessory - labelled as TVKC in the Ordering Codes section. The thermal fuse link releases the coupling mechanism when the air temperature in the damper exceeds 72�C. Additional Details Additional Details Delivery This item is usually stocked overseas and takes about 2-3 weeks to deliver. If stock in UK deliverable in 3-4 days. Enquire on 01729 824108 Brand Systemair Warranty 1 year manufacturers warranty