Find The Needle Add My Company
ADT111C - Temperature/Thermocouple Trip Amplifier with Single Ten Turn Dial Calibrated for set point (Dual dial image shown)

Our ADT111C is a Din Rail Mounted Temperature/Thermocouple Input Trip Amplifier with a ten turn dial calibrated for set point which is suitable for combinations of process inputs and SIL1, SIL2 rated (EN 51508-2) safety instrumented system (SIS) loop applications, as 1oo1 architecture (HFT:0).Input is any mV signal developed from any thermocouple type B, J, K, N, R, S or T, with a minimum 4mV span (automatic cold junction compensation as standard)Trip output is a set of changeover contacts (D.P.C.O) rated at 250VAC, 2A, 100VA resistive as standard.

Environmental Condition

Performance

Mounting/Dimensions

Environmental Condition

Storage Temperature: -40°C to +70°COperating Ambient: -15°C to +55°CRelative Humidity: 5% to 95% RH (Non-Condensing)

Performance

Trip settability: ±0.1% (Ten-Turn Calibrated Dial on front fascia)Trip repeatability: ±0.1% Response time; <200mS (0-100% step change)Consumption: <3VA

Mounting/Dimensions

Enclosure: 50w x 75h x 145d mm

Mounting: Din Rail (TS35) or Surface by corner fixing holes