Current Transducers-Premo-DCT200Amp
Product Code: DCT200A Current Transducer
* High Accuracy over high bandwidth.
* Very low output noise and offset drift.
* Negligible insertion losses.
* High immunity to interference.
* Overload Capability.
* Excellent linearity.
General Data:
* Operating Temperature: -20 to 70 ºC
* Storage Temperature: -20 to +85 ºC
* Weight: 300g
* Primary Diameter Hole: < 12mm
* Basic Insulation (Between Primary and Measurement Current): 3500 V AC 50Hz 1'
* Fault Operation Condition (Led Power Off): Ip > 120%
* Compensation Winding Maximum Resistance (T= 70ºC): 40 Ohm
* Lenght Two Wire Cable to R Burden (Connected between pin 1 and 3): 50cm (typical)
Accuracy:
* Accuracy at Ip (T=25ºC): < 0.1%
* Linear Error ( Beetwen 50 to 200 A) Vcc = ±15V, Rb = 2.7 Ohm: < 5 ppm
* Linear Error ( Beetwen 10A to 50A ) Vcc = ±15V, Rb = 27 Ohm: < 10 ppm
* Linear Error ( Beetwen 0.01 to 10A ) Vcc = ±15V, Rb = 50 Ohm: < 50 ppm
* Offset Current: 5uA Max
* Offser Current Temperature Drift: < 5 ppm/ºC
* Time Response ( 10% to 90% of Ip): <1us
* di/dt Followed Accurately: > 100A/us
* Frequency Bandwidth ( Ip = 10A DC): DC to 100kHz ( -3dB )
Applications:
* AC variable speeds drives and servo motors.
* Battery supplied applications.
* Uninterruptable Power Supplies (UPS).
* Static converters for DC motors.
* Switch mode power supplies (SMPS).
* Power supplies for welding applications.
According To:
* UNE EN 50178
* UNE EN 50155