Find The Needle Add My Company
LQM III Heat Meter Assembly Max 90 °C : 1/2" Qn 1.5 m3/hr (kW,mW and mJ, GJ shown)
LQM III Heat Meter Assembly: 1/2" Qn 1.5 Complies with OIML R75, EN1434 (kW,mW and GJ) Meter mm inches 15 1/2'' Qmax m³/h 3 Qn m³/h 1.5 Qt l/h 120 Qmin l/h 30 PN bar 16 Pressure loss bar < 1 Starting flow l/h < 10 Minimum reading lt 0.05 Remote meter kit includes: 5yr Battery Powered Integrator (IP54 rated) 1/2" Mechanical Water Meter 90 °C H,V / K=1 Horizontal or Vertical Installation Supplied with Nuts, Tails & Washers 3 Metre Pt 500 Temp Probes + Pockets RS232 & RS485 Data ouput (See Options) Pulse Output (See options) M-Bus Output/EN 1434 (See options) TRANSMITTED DATA User number Error code Serial number Energy Volume Power Flow rate Higher temperature Lower temperature Temperature differrence Tarriff energy Time of operation Time of operation with error Time and date of calculator clock Average temperature for last 24 h (higher) Average temperature for last 24 h (lower) Average flow rate for last 24hours The LQM III Integrator has the option to be used as a dual channel Energy meter for Hot or Chilled systems, with the addition of another flow meter and temp sensors. See data sheet for further options.

For more information on LQM III Heat Meter Assembly Max 90 °C : 1/2" Qn 1.5 m3/hr (kW,mW and mJ, GJ shown) talk to Bell Flow Systems

Enquire Now

  Please wait...

Location for : Listing Title