Find The Needle Add My Company
T&R KV30-100 MK2 Test System
The T&R KV30-100 mk2 and KV50-100 mk2 are high power, high voltage AC test systems designed for insulation testing. These systems are equally suited to both development and routine testing of electrical insulation systems and plant. The equipment consists of a control unit and a separate oil filled high voltage transformer, linked by a 5 metre supply and control cables. The control unit is fitted with a comprehensive range of facilities for control, metering and protection. The output voltage and current are displayed on large, linear analogue instruments, and a variable electronic trip is provided, allowing the trip current to be set to 10-110% of rated output. FEATURES 0-30kV output voltage. 3kVA output capability. Key operated supply switch to prevent unauthorised operation. Dual overload protection. Variable electronic trip - 10-110% of rated output. Voltage and current metering. External interlock circuit. Zero-volt interlock. Visual indication of test piece failure. T&R KV30-100 MK2 High Voltage AC Test System Output Continuous Ratings KV30-100 mk2 KV50-100 mk2 Voltage 0-30kV AC 0-50kV AC. Current 50mA 50mA. Power 1.5kA 2.5kA. Intermittent Ratings (5 Mins On/15 Mins Off) KV30-100 mk2 KV50-100 mk2 Voltage 0 to 30kV AC 0 to 50kV AC. Current 100mA 100mA. Power 3kVA 5kVA. Dimensions 370 x 480 x 290 mm. Weight 25 kg. Transformer weight 210 kg. Transformer dimensions 480 x 460 x 570 mm.